Battery Cabinet Matrix - 480 VDC
Home > Technical Documents > Matrix-480



Notes:
- Battery charts are calculated from Power Battery PRC/TC Discharge Rates.
- Cabinets dimensions are specified for side by side installation. Consult factory for other layout dimensions.
- Ratings above 90 minutes are specified at 1.75 volts per cell. Please adjust the cut off voltage for these runtimes.
- Systems that require flame retardent batteries can be ordered by adding "TC" to the part #. ( Ex: 1CR4-40TC150C-480) 5
- Systems are fused for over-current protection unless a breaker is added.
- Circuit breakers per system or per string are optional. Normally sized so 1 string can be tripped with remainning strings online.
Circuit Breaker Adder:
- To add a breaker per string, add the breaker part # to the system Part #. (Ex. 1CR4-40TC150C-480-H100)
- To add an option to the circuit breaker, add the breaker option part # to the system part #. (Ex. 1CR4-40TC150C-480-H100-S)
- When adding a UVR or Shunt trip to a breaker, please specify the voltage required. (Ex. 1CR4-40TC90S-480-H100-S120)
- To add a breaker per string for multiple string system, add the Qty of breakers to the systems part #. (Ex. 3CR4-120120S-3H400)
Power Plus systems:
- Internal chargers can be added to any CR System, when the system is being used in conjuction with a small KVA ups that has a small internal charger.
- Please see the Power Plus cut sheet and price guide for the adder information.